Duke Technology Co., Ltd.
|
Price: | 1.0 USD |
Payment Terms: | T/T,L/C,WU,Paypal |
Place of Origin: | Beijing, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Technology:
The DK-200F oil gas analyzer can realize gas analysis in multi-component oil, and the high-sensitivity measurement of short-path optical path can be realized by Finnish interference company's photoacoustic spectroscopy technology. Ultra-high sensitivity based enhanced cantilever beam Optical microphone technology enables linear dynamic range ratios up to 5 steps. Ultra-high sensitivity is achieved with 7 optical narrow-band filters. Extremely narrow optical filtering removes background gas interference; multiple spectral regions can be beneficial The smallest cross-sensitivity. The multi-gas analyzer is based on infrared photoacoustic spectroscopy technology. It has a pulsed infrared light source and passes through a narrow-band optical filter to form seven spectral bands in the mid-infrared region for gas analysis.
Characteristic:
Sub-ppm detection limit
The oil and gas separation speed is fast, and special environmental adaptation technology is adopted to eliminate the influence of temperature and humidity changes on the gas distribution coefficient.
High anti-interference performance, electromagnetic compatibility performance meets gb/t17626 and iec61000 standards
Provide two levels of alarm function, alarm signal can be transmitted remotely
Open database for access to power system LAN
Faster analysis cycle with a minimum monitoring period of 10 minutes, which can be set by the user. The recommended detection period is 12 hours.
The system has a secondary gas threshold alarm and a growth rate alarm function, and the alarm concentration and growth rate can be set arbitrarily.
Equipped with an expert system for judging latent faults, the latest fault diagnosis technology uses the iec60599 standard and the improved fuzzy three-ratio method, David triangle, cubic graphic method and other methods.
It has historical data trend graph query, report format display and printing function, which is convenient for longitudinal comparison of monitoring data to analyze transformer operation and fault development trend.
Support iec 61850 communication standard, optical fiber or twisted pair optional
High degree of system integration, optional with core ground current and ambient temperature and humidity monitoring function
Double-circuit multi-mode constant temperature control, temperature control accuracy of ± 0.1℃, equipment equipped with automatic constant temperature industrial air conditioner
Functional interface circuit adopts optocoupler isolation design to further improve system anti-interference performance
Full digital, remote data transmission, control and parameter settings with Ethernet
Highly scalable for easy integration with other monitoring devices
Analysis software man-machine interface friendly, full Chinese interface, easy to operate, rich system features
The core unit is a standard 19-inch rack structure with a compact structure, small size, easy maintenance and group screen
Technical parameter:
Technical specifications | |||||
Range | |||||
Gas | Lower limit / ppm | Upper limit / ppm | |||
Hydrogen | 5 | 5,000 | |||
Methane | 1 | 50,000 | |||
Ethane | 1 | 50,000 | |||
Ethylene | 1 | 50,000 | |||
Acetylene | 1 | 50,000 | |||
Carbon monoxide | 5 | 50,000 | |||
Carbon dioxide | 5 | 50,000 | |||
Oxygen | 0% | 100% | |||
Nitrogen | 0% | 100% | |||
Moisture measurement with micro water | 0% | 100% | |||
Physical and mechanical | |||||
Ambient operating temperature | +5 - +50℃ | ||||
Operating sample temperature | 0 - +45℃ | ||||
Storage temperature | -30°C - +80℃ | ||||
Humidity | 90% (non-condensing @30℃) | ||||
Vibration tolerance | IEC 60068-2-6, Fc test | ||||
Drop/Shock | Iec 60068-2-31 and ista 1a | ||||
Main power input frequency range | 47-63Hz | ||||
Main power input voltage range | Universal 90-250vac | ||||
Weight | < 15kg | ||||
Size | 1210pxW x 347.5pxH x 1100pxD (19.1In W x 5.5 in H x 17.3 in D) | ||||
Gas chamber volume | < 30ml | ||||
Oil volume in the extraction unit | <= 50ml | ||||
Dynamic range | 500-50,000 | ||||
Zero drift | ± detection limit / 1 month | ||||
Measurement repeatability | 5% of the measured value under reference conditions | ||||
Range drift | 5% of measured value / 12 months | ||||
Precision | +/- 5% or +/- 2 ppm (whichever is greater) +/-1% rh (H2O relative humidity is 0-90%) | ||||
standard | |||||
EN61326-1:2006 | Radiation emission (A level ) | ||||
EN61326-1:2006 | Conducted emission (A level) | ||||
EN61000-3-2:2000 | Steady state and wave harmonics | ||||
EN61000-3-3:2001 | Flicker test | ||||
IEC61000-4-2:2001 | Electrostatic discharge immunity test | ||||
IEC61000-4-3:2002 | Radiation immunity | ||||
IEC61000-4-4:2001 | Fast electrical transient/burst immunity test | ||||
IEC61000-4-5:2001 | Surge immunity | ||||
IEC61000-4-6:2001 | Conducted radio frequency immunity | ||||
IEC61000-4-8:2001 | Magnetic field immunity | ||||
IEC61000-4-11:2001 | Voltage dips and interruptions | ||||
Other | EN 61010-1:2001 IEC61010-1 UL61010-1 CAN/CSA-C22.2 No.61010-1 EN 50270:2006 |